Product Features
| :: |
User-Customisation
through Scrolling Menu, 14-Segment LED
- intuitive user interface guides user
easily through setup functions |
| |
|
| :: |
Multi Measurement Range-
User Selectable |
| |
|
| :: |
Galvanically Isolated 4-20
mA Output for remote monitoring or hardcopy
recording |
| |
|
| :: |
Universal Power Supply Input
from 85 to 250 VAC/DC allows use at multiple
sites and withstands voltage fluctuations
|
| |
|
| :: |
Two Level Password Protection
prevents un authorized tampering with
settings |
| |
|
| :: |
Automatic Temperature Compensation
with 3-wire Pt 100 system ensures accurate
readings under fluctuating temperatures
|
| |
|
| :: |
Adjustable Temperature Coefficient
(0.0 to 5.0%/oC) and selectable cell constants
for more accurate measurements |
| |
|
| :: |
Adjustable Hysteresis (Dead
Band) prevents rapid contact switching
near set point |
| |
|
| :: |
Non-Volatile Memory retains
all stored parameters and calibration
data even if power fails |
| |
|
| :: |
Easy Installation and Wiring
with detachable plug-in connectors |
Applications
CON 200: Use
for plating tank, rinse water, boiler and
cooling tower, feed water and blowdown control,
font solution make-up and control for printing,
photographic developing, chemical production
process, ion exchange systems, R.O. systems,
industrial process water, wastewater, dilute
acids, salts and bases.
Specifications
|
Product
Specification |
Description |
| Conductivity
Range |
0.00
– 20.00 µS/cm
0.0 – 200.0 µS/cm
0.0 – 200.0 µS/cm
0 – 2000 µS/cm
0.00 – 10.00 mS/cm
0.00 – 20.00 mS/cm
0.0 to 200.0 mS/cm
0.0 – 200.0 mS/cm |
0.1
µS/cm
0.1 µS/cm
1 µS/cm
1 µS/cm
1 mS/cm
1 mS/cm
1 mS/cm
10 mS/cm |
| Accuracy |
±
1% of full scale |
| Temperature
Range |
-10
to 110 °C |
| Resolution
& Relative Accuracy |
0.1
°C & ±0.5 °C |
| Temperature
Sensor |
Pt
100 (3-wire) |
| Temperature
Compensation |
Auto
/ Manual (0°C to 100°C) |
Temperature
Coefficient |
0.0
to 5.0 % |
| Set
Point and Controller Functions |
| Function |
Limit Control |
| Switching
Hysteresis |
10%
of full scale |
| Contact
Outputs, Controller |
2
SPDT relays |
| Switching
Voltage/ Current/ Power |
Max
250 VAC/ Max 3A/ Max 600 VA |
| Electrical
Data and Connections |
| Power
Requirement |
85
to 260 VAC, 50/60 Hz or DC |
| Signal
Output/ Load |
4-20mA
galvanically isolated / 200Ω |
| Connection
Terminals |
3
detachable connectors (3-pin; 7-pin
& 9-pin terminal blocks) |
| Main
Fuse |
250mA,
Anti-surge (BUSSMAN S504 + 250mA) |
| Environmental
Conditions |
| Maximum
Relative Humidity |
10
to 95% (Non-condensing) |
| Ambient
Temp. Operating Range |
-10 to 50 °C (14 °F to 122°F) |
| Mechanical
Specifications |
| Dimensions |
96
x 48 x 150 mm |
| Weights |
300
g (boxed) |
Order Information
|
Order
No. |
Item |
| TSCONCTP0200 |
alpha
COND 200 Conductivity analyser with
4-20mA output and 85-250 VAC/DC (Unit
only). |
Sales
Enquiry
Service
Enquiry
Products > By Type > Controllers
& Transmitters Series