| Industrial
Process Controllers & Monitors
alpha-pH200
1/8 DIN pH/ORP Controller
-
User-Customisation
through Scrolling Menu, 14-Segment LED - intuitive
user interface guides user easily through setup functions
-
Symmetrical Mode
Operation eliminates electronic noise problems when used with
solution ground
-
Galvanically Isolated 4-20 mA
Output for remote monitoring or hardcopy recording
-
Universal
Power Supply Input from 85 to 250 VAC/DC allows use at
multiple sites and withstands voltage fluctuations
-
Two Level Password
Protection prevents un authorized tampering with settings
-
Automatic Temperature
Compensation with 3-wire Pt 100 system ensures accurate readings
under fluctuating temperatures
-
Adjustable Hysteresis
(Dead Band) prevents rapid contact switching near set point
-
Non-Volatile
Memory retains all
stored parameters and calibration data even if power fails
-
Easy Installation
and Wiring with detachable plug-in connectors
Applications
General: Ideal
for virtually any batch type application where pH or ORP control or
adjustment is needed. Use as ORP monitor for ozone systems and general
purpose pH monitor for all types of water treatment and chemical processes.
Aquaculture: Use
for pH or ORP control in fish ponds and tanks.
Industrial:
Use to treat batches of incoming process water, rinse water
treatment, recirculating system and wastewater treatment. Suitable
for pH or ORP control of plating tanks and chemical processing tanks.
Ideal for low cost monitor with alarms for batch and process applications.
Perfect for wastewater neutralization in small and medium sized batches.
Specifications of alpha-pH200
Controller
| Product
Code |
EC-PHCTP0200 |
pH
Range |
0.00
to 14.00 pH |
Resolution
& Accuracy |
0.01
pH & ±0.01 pH |
mV
Range |
-999
to 1000mV |
Resolution
& Accuracy |
1/
±2.0 mV |
Temperature |
-10
to 110°C |
Resolution
& Accuracy |
0.1/
±0.5°C |
Sensor |
Pt
100 (3-wire) |
Temperature
Compensation |
Automatic/
Manual (0 to 100°C) |
Set-point
and Controller Function |
Function |
Limit
Control |
Switching
pH/ ORP Hysteresis |
0.00
to 2.00 pH/ 0 to 300 mV |
Contact
Outputs, Controller |
2
SPDT relays |
Switching
Voltage/ Current/ Power |
Max
250 VAC/ Max 3A/ Max 600 VA |
Electrical
Data and Connections |
Power
Requirements |
85
to 260 VAC, 50/60 Hz or DC |
Signal
Output/ Load |
4-20
mA galvanically isolated/ 200 ohms |
pH/
ORP Input |
BNC
(1012 W Impedance) |
Connection
Terminals |
3
Detachable connectors (3-pin, 7-pin & 9-pin terminal
blocks) |
Main
Fuse |
250
mA, Anti-surge (BUSSMAN S504 + 250mA) |
Environmental
Conditions |
Ambient
Temp. Operating Range |
-
10 to 50 °C |
Rel.
Humidity |
10
to 95 % ( non-condensing) |
IP50
- Protection from dust; limited entrance (no harmful deposit),
but no protection against liquid. |
Yes |
Mechanical
Specifications |
Dimensions
(Control Panel Housing- W X H X D) |
96
X 48 X 150 mm |
Weight |
300g
(350g when boxed) |

 
Copyright © 1997 Eutech