| Industrial
Process Controllers & Monitors alpha-RES1000
1/4 DIN Resistivity Controller
-
Two Selectable Resistivity
Measurement Ranges in one controller
via its IP54 front panel. High-level accuracy of ±1% of full scale
can be obtained with appropriate cells and correct temperature
coefficient
-
User-Customization
through Advanced Setup Menu offers flexibility in matching
the controller's functions to suit individual's specific requirement
-
Choice of Cell
Constant (0.01, 0.1)
for accurate control in any solution
-
Hold Relay for
use with float switches/flow switches and other controllers as
a failsafe function
-
Two Level Password
Protection prevents un authorized tampering with settings
-
0 to 2000 Second
Time Delay Adjustment on control and alarm delays
-
Two
Galvanically Isolated Scalebale 0-20/4-20 mA
Outputs
-
Wash Contact Relay
controls electrodes cleaning systems at desired duration and
frequency
-
Adjustable Hysteresis
(Dead Band) prevents rapid contact switching near set point
-
Non-Volatile
Memory retains all
stored parameters and calibration data even if power fails
-
Line Resistance Compensation
against intrinsic cable resistance for longer cable connection
- Large Dual Display shows measurement
with temperature simultaneously - features clear multiple icons,
set points, and status messages
- Choice of Temperature
Sensor Pt100/Pt1000
with 2-wire or 3-wire temperature input selection
- Easy Installation and Wiring
with detachable plug-in connectors
Applications
General: Use for virtually any
batch or online applications where rapid, accurate control. Great
for OEM/system integrator.
Water Purification/Treatment:
Suitable for pure, ultrapure, and reagent grade water batches of incoming
process water.
Regulatory: Hook to recorder to
document data for regulatory compliance.
Specifications
of alpha-RES1000
Controller
Product
Code |
EC-RESCTP1001/2 |
Resistivity
Range |
0.000-1.999;
0.00-19.99 Mohm |
Resolution
& Accuracy |
0.001;
0.10 Mohm & 1% Full Scale |
Temperature
Range |
-9.9
to 125.0 °C |
Resolution
& Accuracy |
0.1
°C & ± 0.5 °C |
Temperature
Compensation |
Ultra-pure
water or linear (0.00 to 10.00%) |
Type
of Controller Setting |
Limit |
Pickup/Dropout
Delay |
0
to 2000 seconds |
Signal
Output Range (0/4 - 20 mA) |
Max.
100% Full Scale; Min. 10% Full Scale |
Sensor
(for ATC) |
PT100/PT1000 |
No. of Relays
Maximum Voltage
Maximum Current
High/Low Hysteresis Band |
2
SPDT; 1 Alarm
250 VAC
3A;
0 to 10% Full Scale |
Contact
Set-points |
Lo/Lo;
Lo/Hi; Hi/Lo; Hi/Hi (selectable) |
Alarm
Function |
Latching
/ Pulse (software) |
| Insulation
(Front / Housing) |
IP
54 / IP 40* |
Power |
120
or 240 VAC, 50/60 Hz |
Dimensions |
1/4
DIN (96 x 96 mm) |
IP
54 - Protection from dust; limited entrance (no harmful deposit) and
water sprayed from all directions; limited entrance allowed.
IP
40 - Protection from solid objects more than 1 mm (e.g., small wires)
but no protection against liquid.

 
Copyright © 1997 Eutech
Instruments Pte Ltd. marketing@eutechinst.com
|